Transient Monitoring Function based Fault Classifier for Relaying Applications
Abstract
This paper proposes Transient monitoring function (TMF) based fault classification approach for transmission line protection. The classifier provides accurate results under various system conditions involving fault resistance, inception angle, location and load angle. The transient component during fault is measured by TMF and appropriate logics applied for fault classification. Simulation studies using MATLAB®/SIMULINK™ are carried out for a 400 kV, 50 Hz power system with variable system conditions. Results show that the proposed classifier has high classification accuracy. The method developed has been compared with a fault classification technique based on Discrete Wavelet Transform (DWT). The proposed technique can be implemented for real time protection schemes employing distance relaying.
Keywords
Full Text:
PDFDOI: http://doi.org/10.11591/ijece.v8i6.pp4089-4095
This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.
International Journal of Electrical and Computer Engineering (IJECE)
p-ISSN 2088-8708, e-ISSN 2722-2578
This journal is published by the Institute of Advanced Engineering and Science (IAES) in collaboration with Intelektual Pustaka Media Utama (IPMU).